Enter design current and corrected cable ampacity to select a preliminary standard breaker and verify load, breaker, and cable coordination.Start calculating
A / mm²Current and protectionPDFStandalone reportSBC 401Method reference
Calculator
Enter your data and see the result immediately
Select a preliminary standard breaker rating and check load-to-breaker-to-cable coordination using IEC or NEC continuous-load treatment.
The next standard rating after the continuous-load margin, when selected.
Load current24A
Design current24A
Suggested breaker25A
Cable ampacity checkPreliminarily passes
Entered cable ampacity34 A
Selection basisSBC 401 / IEC
Continuous-load multiplier100%
Calculation method
Preliminary overload coordination: load current Ib ≤ breaker In ≤ corrected cable ampacity Iz.
Engineering notes
Also verify fault current, interrupting rating, disconnection time, selectivity, trip curve, and load type.
Safety approval
Do not use this estimate for installation before checking nameplate data, site conditions, short-circuit protection, and earthing.
This is a planning and comparison estimate. Final protection and conductor selection requires review by a licensed engineer or electrician, site-condition checks, manufacturer instructions, and the applicable code.
Calculation guide
How is a circuit breaker selected?
Under the IEC method, design current Ib must not exceed breaker rating In, while In must not exceed corrected cable ampacity Iz. The calculator reports coordination instead of merely selecting the next rating above load.
Choose IEC treatment or NEC continuous-load treatment. Trip curve, motor starting, breaking capacity, and prospective fault current remain essential site-specific checks.
Breaker selection steps
Enter the circuit design current.
Identify continuous-load treatment.
Enter corrected cable ampacity.
Choose IEC or NEC basis.
Verify Ib ≤ In ≤ Iz, then review curve and breaking capacity.