Convert warehouse dimensions into required airflow, then compare fan performance at operating pressure to estimate quantity and duct size.Start calculating
Calculate warehouse ventilation in CFM and m³/h, exhaust fan quantity, selection airflow, and preliminary duct size from volume, ACH, and rated fan capacity.
Calculator
Exhaust fan calculator
Bathroom, kitchen, office, or warehouse
Calculation inputsResults update instantly
Study resultTAYAR TK
Preliminary engineering studyExhaust fan calculator
Required airflow from room volume and air changes, including minimum bathroom or kitchen airflow.
Net required airflow24,000m³/h
Required airflow14,125.96CFM
Fan quantity5fans
Preliminary standard duct1,400mm
Room volume4,800 m³
Airflow by ACH24,000 m³/h
Reference minimum0 CFM (entered)
Selection airflow with reserve27,600 m³/h
Single-fan capacity at operating pressure6,000 m³/h
Calculated hydraulic diameter1,276 mm
Design air velocity6 m/s
Calculation method
Net airflow is the greater of volume × ACH and the reference minimum; selection airflow = net airflow × (1 + reserve).
Engineering notes
Bathroom ACH is compared with ASHRAE/HVI: 50 CFM intermittent or 20 CFM continuous, with fixture-based sizing for large bathrooms.
Kitchen hoods use the HVI recommendation by hood width and location plus the ASHRAE minimum; recirculating hoods are not ventilation.
Select an HVI- or AMCA-certified fan from its curve at actual duct resistance, not its free-air rating.
Safety approval
Hazardous fumes, heat, commercial kitchens, and process ventilation require specialist design.
This is a planning and comparison estimate. Final protection and conductor selection requires review by a licensed engineer or electrician, site-condition checks, manufacturer instructions, and the applicable code.
Calculation guide
How is warehouse ventilation calculated?
Warehouse volume is multiplied by the selected air changes per hour to calculate m³/h. ACH depends on storage, heat, contaminants, people, and processes, so it remains an editable engineering input.
Fan quantity uses selection airflow divided by certified fan performance at operating pressure. Supply and exhaust openings must avoid short-circuiting, while hazardous or fire-sensitive storage requires specialist design.
Warehouse fan estimation steps
Enter clear internal dimensions.
Select ACH for the actual activity.
Add a reasonable system reserve.
Enter certified fan airflow at pressure.
Distribute exhaust and make-up air across the space.
Before selecting fans
Internal heat, moisture, and contaminants.
Louvre, filter, duct, and bend resistance.
Make-up air opening size and location.
AMCA-certified or clearly documented fan performance.